Trial / Demo
ApacheSim fails and gives an Error: Element STD_CEI_ in room 'FF Lift' [60000002] has no corresponding element in room 'GF Lift' [60000000]
(Elements and rooms names can be different, depending on the used model)
This is a geometry-related error, it means an adjacency is not seen similarly by both sides (i.e. a different area is seen by the room on one side from the room on the other side).
Check both rooms visually for any geometry flaws and fix them, then rebuild the model's adjacencies (Settings >> Model >> Rebuild Model Adjacencies). Sometimes, the two rooms can be a bit far from each other, or a small surface between the two rooms is not picked up entirely by both.
If that does not work, try redrawing the rooms.